Product Details:
1-Square D Custom CMM Swbd-QED-2 Switchboard
---------------------------------
Square D Custom CMM Swbd
Designed and Tested in accordance with:
UL 891/NATIONAL ELECTRIC CODE/NEMA PB-2
System Voltage - 480Y/277V 3Ph 4W 60Hz
Source Description - Six Circuit Mains
System Ampacity - 800A
Bussing - Aluminum Plated w/Tin and Copper
Plated w/Silver
Neutral Bus - 100%
Max Available Fault Current (RMS) - 65kA
Enclosure - Type 1
Accessibility: Front Only
Rodent Barrier
Exterior Paint Color - ANSI 49
Ground Lug provided for each device
Aluminum Ground Bus
Dimensions
---------------------------------
1 - 24" Wide Section(s)
1 - 30" Wide Section(s)
1 - 36" Wide Section(s)
3 - 24" Deep Enclosure(s)
Dimensions: 90.00" W X 24" Max D X 91.5" H
Approximate Weight: 1854.00 lbs / 840.97 kgs
Incoming Requirements
---------------------------------
Suitable for Use as Service Entrance When Not
More Than 6 Main Disconnecting Means are
Provided
Entry Point: Center of Lineup, Through the
Bottom
Connection Type: Cable in Bussed Auxiliary
EUSERC Terminals per Turlock Irrigation Dist
(CA) provided
Incoming Utility Metering Compartment is NOT
provided
Mains
---------------------------------
1 - 200A/200A 480V 80% Rated 3 Pole Tenant
Main, EUSERC Meter Socket and Thermal
Magnetic Circuit Breaker: Type JJ
Main One
Padlock Attachment
1 - 500AT 480V 80% Rated 65 kA 3 Pole UL,
Group Mounted Basic Electronic Trip
Circuit Breaker: Type MJ
Main Two
Associated to Group Mounted Utility 1
Padlock Attachment for M-frame
1 - 100AT 480V 80% Rated 65 kA 3 Pole UL,
Group Mounted Thermal Magnetic Circuit
Breaker: Type BJ
Main Four
Associated to Group Mounted Utility 1
Padlock Attachment
1 - 100AT 480V 80% Rated 65 kA 3 Pole UL,
Group Mounted Thermal Magnetic Circuit
Breaker: Type BJ
Main Three
Associated to Group Mounted Utility 1
Padlock Attachment